|
A stairway should
be of sufficient width for the number of people who are likely to
use it in an emergency and it should not normally be less than 1
metre wide. However, a narrower one may be adequate if you are sure
that only a few people, who are familiar with the stairway, will
use it.
Where more than
one stairway is provided, you should assume that the widest one
may be unusable as a result of the fire. This means that the remaining
stairway(s) will need to provide a satisfactory escape route for
everyone present.
There may be
no need for you to discount the widest stairway where each stairway
is reached through a protected lobby. Certain other compensatory
features, such as sprinklers or smoke control systems, may also
be considered.
Stairways should
normally be protected by fire-resisting partitions and fire-resisting,
self-closing doors (except toilet doors) and lead directly to a
way out of the building. An unprotected stairway may, however, be
suitable in workplaces of low or normal fire risk, provided that:
the stairway links no more than two floors and those floors
are not linked to another floor by an unprotected stairway;
and
it is additional to that required for escape purposes;
and
no escape route from a dead-end situation on an upper floor
passes the access to such a stairway.
People should
not have to pass through a protected stairway to reach an alternative
stairway. Where this cannot be achieved, a stairway may be by-passed,
for instance by using doors connecting adjacent rooms. In such situations
the doors should be kept free from obstruction and available for
use at all times.
A single stairway
may be suitable for means of escape in workplaces of low or normal
fire risk, provided that people on each floor can reach it within
the appropriate travel time (see details of distances earlier in
this section). It also needs to:
be constructed as a protected stairway and serve no more than
three floors above, or one floor below, ground level;
be accessed, other than at the top floor, by means of a protected
lobby or protected corridor;
be of sufficient width to accommodate the number of people
who may need to use it in an emergency; and
lead direct to open air.
There is no
need for you to provide protected lobbies where the workplace is
of low fire risk. This also applies to workplaces of normal fire
risk, provided that either an automatic fire detection system or
sprinklers linked directly into the fire alarm system are installed
in the rooms or areas leading directly onto the protected stairway.
In small workplaces
of low or normal fire risk, unprotected stairways (including a single
stairway) may be satisfactory as a means of escape, provided that:
the stairway provides access between the ground and first
floor and/or ground floor and basement only, and an exit can be
reached from any part of those floors within the escape times given
for single escape routes earlier in this section; and
access to the stairway is clearly visible from any part of
the floor it serves and it exits not more than 6 metres from a storey
exit leading direct to open air at ground level.
Where an external
stairway is provided, any door or window (other than toilet windows)
opening onto the stairway, or within 1.8 metres horizontally or
9 metres vertically of it, should be fire-resisting. Windows should
be unopenable and doors should be self-closing.

In exceptional
circumstances, a small number of unprotected, openable windows may
be allowed, provided that the rooms containing them are separated
from the rest of the building by fire-resisting construction and
the external stairway is not the only one from the upper storeys.
Your workplace
may have stairways that are not needed as part of the formal means
of escape. These stairways are known as accommodation stairs and
will not need to be protected, provided that:
they do not serve protected corridors;
they do not link more than two floors; and
people do not have to move towards the head of an unprotected
stairway to make their escape.
Means
of escape for use by staff
|
The features
listed below are not normally acceptable as a means of escape for
members of the public as they are not conventional escape routes.
However, they may, in certain circumstances, be used by a small
number of staff if they are trained to do so or use the exit during
their normal work activity:
revolving doors (except those specifically designed for escape
purposes);
portable, foldaway, vertical-raking or throw-out ladders;
window exits;
wicket doors and gates;
wall and floor hatches; and
rolling shutters and folding, sliding or up-and-over doors.
Lifts should
not be used as a means of escape, but see 'Use
of lifts as means of escape' on page 70 for details on the evacuation
of disabled staff.
Reducing
the spread of fire, heat and smoke
|
You should ensure
that any holes in fire-resisting floors or walls, eg pipework openings,
are filled in with fire-resisting materials in order to prevent
the spread of fire, heat and smoke. (See 'How
fire spreads through the workplace' in Part 2.)
You should make
sure that any large area of combustible wall or ceiling linings
is either removed, treated or suitably covered to reduce the possibility
of the linings contributing to the rapid spread of fire. Such linings
must not be used in escape routes. (Information on the suitability
of wall and ceiling linings can be found in the Home Office publication
Guide to the fire precautions in existing places of work that
require a fire certificate. Factories, offices, shops and railway
premises - see the References
section.)
Any exhibition
or display with large amounts of flammable materials, such as paper,
textiles and cotton wool, can allow fire to spread rapidly. You
should therefore avoid using such materials wherever possible. Any
permanent or semi-permanent displays, including wall displays, should
ideally be placed behind glass.
Noticeboards
should be kept as small as possible and should be fixed securely
in position. They should not be continuous along the length of a
wall, sited above heaters etc or contain an excessive amount of
paper (eg overlapping or multi-sheet notices).
Defining
the escape route
|
The contents
of any room in which people are working or any open floor area to
which the public are admitted should be arranged to ensure that
there is a clear passageway to all escape routes. This may mean
that you will need to clearly define the routes, for example by
marking the floor or by providing a contrasting floor covering.
Items
prohibited on an escape route
|
You should make
sure that items which pose a potential fire hazard or those which
could cause an obstruction are not located in corridors or stairways
intended for use as a means of escape. In particular, the following
items should not be located in protected routes, or in a corridor
and stairwell which serves as the sole means of escape from the
workplace, or part of it:
portable heaters of any type;
heaters which have unprotected naked flames or radiant bars;
fixed heaters using a gas supply cylinder, where the cylinder
is within the escape route;
oil-fuelled heaters or boilers;
cooking appliances;
upholstered furniture;
coat racks;
temporarily stored items including items in transit, eg furniture,
beds, laundry, waste bins etc;
lighting using naked flames;
gas boilers, pipes, meters or other fittings (except those
permitted in the standards supporting the building regulations and
installed in accordance with the 'Gas Safety Regulations');
gaming and/or vending machines; and
electrical equipment (other than normal lighting, emergency
escape lighting, fire alarm systems, or equipment
associated with a security system), eg photocopiers.
Doors people
have to pass through in order to escape from the workplace should
open in the direction of travel where:
more than 50 people may have to use the door;
the door is at or near the foot of a stairway;
the door serves a high-fire-risk area (see 'Fire
risk categories for assessing the means of escape' earlier in
this section); or
the door is on an exit route from a building used for public
assembly, such as a place of public entertainment, a conference
centre or exhibition hall.
You should make
sure that people escaping can open any door on an escape route easily
and immediately, without the use of a key. All outward opening doors
used for means of escape, which have to be kept fastened while people
are in the building, should be fitted with a single form of release
device such as a panic latch, a panic bolt, or a push pad.
Where a door
needs to be fastened by a security device, it should be the only
fastening on the door and you will have to make sure that all your
staff know how it works. Such devices are not normally suitable
for use by members of the public. You should display a notice explaining
the method of operation and, if necessary, provide a suitable tool
so that the device can be operated safely.
Where fire doors
are provided they should be fitted with effective self-closing devices
and labelled 'Fire Door - Keep Shut'. Fire doors to cupboards and
service ducts need not be self-closing, provided they are kept locked
and labelled 'Fire Door - Keep Locked Shut'. (Signs should meet
the requirements of British Standard 5499 - see the References
section.)
Self-closing
fire doors may be held open by automatic door release mechanisms
which are either:
connected into a manually operated electrical fire alarm system
incorporating automatic smoke detectors in the vicinity
of the door; or
actuated by independent smoke detectors (not domestic smoke
alarms) on each side of the door.
Where such mechanisms
are provided, it should be possible to release them manually. The
doors should be automatically closed by:
the actuation of a smoke-sensitive device on either side of
the door;
a power failure to the door release mechanism or smoke-sensitive
devices; or
the actuation of a fire warning system linked to the door
release mechanisms or a fault in that system.
Such fire doors
should be labelled with the words 'Automatic Fire Door - Keep Clear'.
Where possible, automatic fire doors should be closed at night and
have an additional sign to this effect. (Automatic release mechanisms
should comply with British Standard 5839: Part 3.)
Other automatic
devices are available which operate on different principles - you
should consult your local fire authority before installing them.
Emergency
escape and fire exit signs
|
Emergency escape
routes and exit doors that are not in common use should be clearly
indicated, as appropriate, by suitable signs. However, in certain
circumstances, such as places of public assembly, you should indicate
all exit doors. All signs should be in positions where they can
be seen clearly. These signs must take the form of a pictogram which
may incorporate a directional arrow. The sign can also be supplemented
by words such as 'Fire Exit'.
Examples
of pictographic fire exit signs
Note: Fire
safety signs must comply with the relevant requirements of the Health
and Safety (Safety Signs and Signals) Regulations 1996 (see the
References section for details of
the relevant guidance).
Continue
|