Lighting
of escape routes
|
All escape routes,
including external ones, must have sufficient lighting for people
to see their way out safely. Emergency escape lighting may be needed
if areas of the workplace are without natural daylight or are used
at night.
Before providing
emergency escape lighting, check the relevant parts of the workplace
with the lights off to see whether there is sufficient borrowed
light from other sources to illuminate the escape route, eg street
lights or unaffected lighting circuits. Where you decide there is
insufficient light, you will need to provide some form of emergency
lighting. Emergency lighting needs to function not only on the complete
failure of the normal lighting, but also on a localised failure
if that would present a hazard.
Emergency escape
lighting should:
indicate the escape routes clearly;
provide illumination along escape routes to allow safe movement
towards the final exits; and
ensure that fire alarm call points and fire-fighting equipment
can be readily located.
In addition
to emergency escape lighting, it may be necessary to provide other
forms of emergency lighting for safety reasons, for example to ensure
that manufacturing processes can be shut down safely.
In smaller
workplaces and outdoor locations with few people, the emergency
escape lighting could take the form of battery-operated torches
placed in suitable positions where
employees can quickly get access to them in an emergency, eg on
an escape route. In other cases, you should provide an adequate
number of electrically operated emergency lighting units, installed
to automatically come on if the power to the normal lighting supply
circuit, which they are connected to, fails.

Typical emergency
lighting units
Emergency lighting
units should be sited to cover specific areas, for example:
intersections of corridors;
at each exit door;
near each staircase so that each flight of stairs receives
direct light;
close to a change in floor level;
outside each final exit;
by exit and safety signs that are required elsewhere following
the risk assessment;
within lift cars;
near fire-fighting equipment; and
near each fire alarm call point.
The lighting
units should be placed as low as possible but at least 2 metres
above floor level (measured to the underside of the lighting unit).
You may need to consider alternative mounting arrangements in areas
where smoke could accumulate and make the lighting ineffective.
Where it is
considered that an electrical emergency lighting system is required,
the system should be installed in accordance with British Standard
5266: Part 1. You should seek the advice of a competent person who
specialises in the installation of these systems.
Smoke
control systems for the safety of people
|
In larger or
complex buildings, a smoke control system may be an effective way
of keeping means of escape routes clear of smoke so that occupants
can evacuate safely.
Smoke exhaust,
using either natural smoke exhaust ventilators or powered smoke
exhaust ventilators, is arranged so that the hot smoke and gases
rise and collect under the ceiling in reservoirs and are then removed
through the ventilators. The aim is to keep smoke at a safe height
above the heads of people using the escape route, while the fire
is still burning.
To achieve this,
any smoke and heat exhaust system and its components should be designed
and installed by a competent person. Guidance on the design of these
systems is in the Building Research Establishment (BRE) reports
Design principles for smoke ventilation in enclosed shopping
centres BR 186, and Design approaches for smoke control in
atrium buildings BR 258. The British Standard Draft for Development
240 Parts 1 and 2 and the CIBSE Fire Engineering Guide also provide
useful guidance. (See the References
section for details of these publications.)
Alternatively,
a smoke control system using a pressure differential system or depressurisation
system can be used to maintain a smoke-free escape route. When using
this form of control, the design, installation and ongoing maintenance
of the system should be in accordance with British Standard 5588:
Part 4.
Buildings
under refurbishment
|
If you decide
to refurbish, redecorate or alter the workplace in a way that affects
one or more means of escape, you will need to make sure that there
are still enough escape routes for the staff (and any others present)
to use should a fire occur.
If your workplace
has a current fire certificate in force, you must inform your local
fire authority before carrying out any structural or material alterations.
You may also need Building Regulation approval and should consult
the relevant building control authority. Other regulations controlling
the safety arrangements in the workplace during construction or
alteration may also apply, such as the Construction (Health, Safety
and Welfare) Regulations 1996. Your local fire authority will be
able to offer you further advice.
Portable
fire extinguishers
|
Portable fire
extinguishers enable suitably trained people to tackle a fire in
its early stages, if they can do so without putting themselves in
danger.
All workplaces
should be provided with means of fighting fire for use by people
in the premises. When you are deciding on the types of extinguisher
to provide, you should consider the nature of the materials likely
to be found in your workplace.
Fires are classified
in accordance with British Standard EN 2 as follows:
| Class
A |
fires involving
solid materials where combustion normally takes place with the
formation of glowing embers; |
| Class
B |
fires involving
liquids or liquefiable solids; |
| Class
C |
fires involving
gases; |
| Class
D |
fires involving
metals; and |
| Class
F |
fires involving
cooking oils or fats. |
Class A and
B fires
Class A fires
involve solid materials, usually of organic matter such as wood,
paper etc. They can be dealt with using water, foam or multi-purpose
powder extinguishers, with water and foam considered the most suitable.
Your risk assessment will help you decide how many you need.
Class B fires
involve liquids or liquefiable solids such as paints, oils or fats.
It would be appropriate to provide extinguishers of foam (including
multi-purpose aqueous film-forming foam (AFFF)) carbon dioxide,
halon* or dry powder types. Carbon dioxide extinguishers are also
suitable for a fire involving electrical equipment.
*Halon
extinguishers are not generally recommended for day-to-day fire
risks because of their ozone-depleting potential. They will be banned
except for defined essential uses after 31 December 2003. For special
risks, one of the other liquefied gas-type extinguishers may be
used.
The fire extinguishers
currently available for dealing with Class A or Class B fires should
not be used on cooking oil or fat fires (but see 'Class
F fires' on page 59).
Class C
fires
Dry
powder extinguishers may be used on Class C fires. However, you
need to consider the circumstances for their use and combine this
with action such as stopping the leak, to remove the risk of a subsequent
explosion from the build-up of unburnt gas.
Class D fires
None of the
extinguishers referred to above will deal effectively with a Class
D fire as these involve metals such as aluminium, magnesium, sodium
or potassium. Only specially trained personnel using special equipment
should tackle such fires. If your assessment identifies the risk
of a fire involving these metals, you should consult your local
fire authority about the best way of dealing with it.
Class
F fires
Special extinguishers
are available for use on fires involving cooking fats and oils,
eg chip pans and deep fat friers, but these should only be used
by specially trained people. (This is not an established class within
the current British Standard but may be added as a new fire classification
when the relevant standard is revised. The class is used in this
guide for ease of reference.)
Types
of portable fire extinguishers
|
The fire-fighting
extinguishing medium in portable extinguishers is expelled by internal
pressure, either permanently stored or by means of a gas cartridge.
Generally speaking, portable fire extinguishers can be divided into
five categories according to the extinguishing medium they contain:
water;
foam;
powder;
carbon dioxide; and
vaporising liquids, including halons.
Some fire extinguishers
can be used on more than one type of fire. For instance, AFFF extinguishers
can be used on both Class 'A' fires and Class 'B' fires. Your fire
equipment supplier will be able to advise you.
The most useful
form of fire-fighting equipment for general fire risks is the water-type
extinguisher or hose reel. One such extinguisher should be provided
for approximately each 200 square metres of floorspace, with a minimum
of one per floor. If each floor has a hose reel which is known to
be in working order and of sufficient length for the floor it serves,
there may be no need for water-type extinguishers to be provided.
Areas of special
risk involving the use of oil, fats, or electrical equipment may
need carbon dioxide, dry powder or other types of extinguisher.
If you are not sure what to provide in any given circumstances,
your local fire authority will be able to advise you. British Standard
5306: Part 3 provides advice about the selection and allocation
of portable fire extinguishers.
Fire extinguishers
should conform to a recognised standard such as British Standard
EN 3 for new ones and British Standard 5423 for existing ones. For
extra assurance, you should look for the British Standard Kitemark,
the British Approvals for Fire Equipment (BAFE) mark or the Loss
Prevention Council Certification Board (LPCB) mark.
Fire extinguishers
may be colour-coded to indicate their type. Previously, the entire
body of the extinguisher has been colour-coded, but British Standard
EN 3: Part 5 (which came into effect on 1 January 1997) requires
that all new fire extinguisher bodies should be red. A zone of colour
of up to 5% of the external area, positioned immediately above or
within the section used to provide the operating instructions, may
be used to identify the type of extinguisher. This zone should be
positioned so that it is visible through a horizontal arc of 180°
when the extinguisher is correctly mounted. The colour-coding should
follow the recommendations of British Standard 7863.
Fire extinguishers,
if properly maintained and serviced, may be in service for at least
20 years. So there may be situations where a building will have
a mixture of new and old fire extinguishers with the same type of
extinguishing medium but with different colour-coded markings. In
these cases and to avoid any confusion, it is advisable to ensure
that extinguishers of the same type but with different colour-coded
markings are not mixed, either at the same location in single-storey
buildings or on the same floor level in multi-storey buildings.
Old-style fire
extinguishers must not be painted red to try and comply with the
new standard, as this would contravene British Standard EN 3 which
covers technical changes during the manufacturing stage.
Fire extinguishers
should normally be located in conspicuous positions on escape routes,
preferably near exit doors. Wherever possible, fire-fighting equipment
should be grouped to form fire points. These should be clearly visible
or their location clearly and conspicuously indicated so that fire
points can be readily identified. Where workplaces are uniform in
layout, extinguishers should normally be located at similar positions
on each floor.
If for any reason
extinguishers are placed in positions hidden from direct view, the
Health and Safety (Safety Signs and Signals) Regulations 1996 require
that their location should be indicated by signs and, where appropriate,
directional arrows. Suitable signs are described in the HSE Guidance
on the Regulations (see the References
section).
Colour-coding of fire extinguishers
Where practicable,
fire extinguishers should be securely hung on wall brackets. Where
this is impracticable, extinguishers should be placed on a suitable
baseplate (not on the floor). To assist in lifting, the carrying
handle of larger, heavier extinguishers should be about 1 metre
from the floor but smaller, lighter extinguishers may be mounted
at a higher level. Make sure that the weight of the equipment falls
below the guidelines recommended in the Manual Handling Operations
Regulations 1992 (see the References
section). This will ensure that extinguishers are easy to handle
and use.
Hose
reels and fire blankets
|
Where hose reels
are provided, they should be located where they are conspicuous
and always accessible, such as in corridors.
Fire blankets
should be located in the vicinity of the fire hazard they are to
be used on, but in a position that can be safely accessed in the
event of a fire. They are classified as either light-duty or heavy-duty.
Light-duty fire blankets are suitable for dealing with small fires
in containers of cooking oils or fats and fires involving clothing.
Heavy-duty fire blankets are for industrial use where there is a
need for the blanket to resist penetration by molten materials.
Hose reels and
fire blankets should conform with relevant British Standards (see
the References section). If you are
unsure about the number or type of portable fire-fighting equipment
or hose reels you need, you should check with the local fire authority
before purchasing any such equipment.
Fixed
fire-extinguishing systems
|
In smaller workplaces,
portable fire extinguishers will probably be sufficient to tackle
small fires. However, in more complex buildings, or where it is
necessary to protect the means of escape and/or the property or
contents of the building, it may be necessary to consider a sprinkler
system.
Sprinkler systems
are traditionally acknowledged as an efficient means of protecting
buildings against extensive damage from fire. They are also now
acknowledged as an effective means of reducing the risk to life
from fire. Systems are being developed which may be suitable for
use in workplaces with residential areas, such as care homes and
houses in multiple occupancy.
Sprinkler systems
need to be specifically designed and installed to the appropriate
hazard category in accordance with an approved code of practice
(eg British Standard 5306: Part 2 - see the References
section, or Technical Bulletins from the Loss Prevention Council
- see Further information). This
will ensure that that the operation of the system will effectively
limit/control the effects of the fire with minimal failures or unwanted
operations (these are usually due to inappropriate use or poor maintenance).
Further information
on the requirements for sprinkler systems, and their benefits, can
be obtained from your local fire authority.
Other
fixed fire-fighting systems
|
In many industrial
and commercial premises, fires can pose a serious threat to the
safety of employees working in or adjacent to areas involving:
process machinery;
electrical switchgear and transformers;
control- and data-processing equipment; and
flammable materials storage.
Fires involving
these risks can effectively be dealt with by the installation of
fixed fire-fighting systems that may be either automatically or
manually operated. For example, process equipment and machinery
which handles flammable substances (eg printing machines, rolling
mills, or oil-filled switchgear), may be protected by extinguishing
systems, using dry powder, foam, carbon dioxide or other inert gas.
However, recent developments using water mist technology mean that
these systems may also be useful, especially in food-processing
areas.
Similarly, protection
of control- and data-processing equipment may be achieved by systems
designed to totally fill the room or the cabinets containing such
equipment with a gas-flooding extinguishing medium to a specified
concentration. These types of systems use a range of gas extinguishing
media. Where there is a possibility that these may discharge into
occupied areas, you need to ensure that the resulting concentration
of the extinguishing medium will not be harmful to anybody present.
Where necessary,
protection of large-scale storage facilities of flammable materials,
especially in bulk tanks, may also be achieved by fixed deluge water
or foam systems.
The design and
installation of fixed fire-fighting systems requires a high level
of expertise, including the ability to carry out a thorough risk
assessment and select the appropriate system and fire-fighting medium.
Such systems have to be specially designed, and can be expensive.
If you are considering installing such a system, you should liaise
with the relevant enforcing authority and consult a reputable company
at an early stage. The British Fire Protection Systems Association
can supply you with a list of companies in your area that undertake
this type of work (see the 'Further
information' section for details).
Continue
|